The RC47 instrument provides for the storage of 4 Set Points and can have up to 3 outputs: relay type or can drive solid state relays type (SSR). The input is programmable and accepts temperature probes (Thermocouples J, K, R, S, T, Thermo-resistances PT100, Thermistors PTC and NTC;) and normalised analogue signals (0/4..20 mA, 0/1..5 V, 0/2..10 V, 0..50/60 mV, 12..60 mV).
Other important available functions are: Loop-Break Alarm function, reaching of the Set Point at controlled speed, ramp and dwell function, Soft-Start function, parameters protection on different levels. If it is powered from Vac line, to avoid breakdown the instrument must be galvanically separated from other components through the use of a transformer.